Combination of power and signal area in one connector, Crimp termination for power and signal area, Use of standard HE and HD contacts
| Inserts | Suitable Shell:10BHood/Housing | 
| Number of contacts | 8/24 | 
| Electrical data acc. to EN 61 984 | |
| Power area | |
| ---Rated current | 16A | 
| ---Rated voltage | 400V | 
| ---Rated impulse voltage | 6kV | 
| ---Pollution degree | 3 | 
| ---Pollution degree 2 also | 10A 250V 4kV 2 | 
| Signal area | |
| ---Rated current | 10A | 
| ---Rated voltage | 250V | 
| ---Rated impulse voltage | 4kV | 
| ---Pollution degree | 3 | 
| Rated voltage acc. to UL/CSA | 600/300V | 
| Insulation resistance | ≥1010Ω | 
| Material | polycarbonate | 
| Limiting temperatures | -40℃...+125℃ | 
| Flammability acc. to UL 94 | V0 | 
| Mechanical working life(mating cycles) | ≥500 | 
| Contacts | |
| Power contacts | |
| ---Material | copper alloy | 
| ---Surface | hard-silver plated | 
| hard-gold plated | |
| ---Contact resistance | ≤1mΩ | 
| ---Crimp terminal | |
| ------mm² | 0.5-4mm² | 
| ------AWG | 20-12 | 
| Signal contacts | |
| ---Material | copper alloy | 
| ---Surface | hard-silver plated | 
| hard-gold plated | |
| ---Contact resistance | ≤3mΩ | 
| ---Crimp terminal | |
| ------mm² | 0.14-2.5mm² | 
| ------AWG | 25-14 |